Constructed for use in Class 1, Division 1, Group D hazardous locations.
|
|
|
Designed
to pump contaminated water, with a wide range of pollutants listed under the UL,
CSA listings. |
|
|
Myers
intrinsically safe control panel
included. |
|
|
Oil-filled
motor for maximum heat dissipation and constant bearing lubrication. |
|
|
UL and
CSA listed. |
|
|
Recessed
impeller reduces radial bearing loads, increasing bearing life. |
|
|
High
torque capacitor start, single phase motor for assured starting under heavy load. |
|
|
Seal
leak probes warn of seal leak condition. |
|
|
On-winding
heat sensors protect motor from overheating and prevents costly motor damage. |
|
| RUGGED SUBMERSIBLE
EXPLOSION-PROOF SUMP PUMPS FOR MUNICIPAL, COMMERCIAL AND INDUSTRIAL USE. DURABLE
MOTOR WILL DELIVER MANY YEARS OF RELIABLE SERVICE. |
Product Capabilites
| Capacities To |
95 GPM
|
360 LPM
|
| Shut-Off Head |
34 ft.
|
10 m
|
| Solids Handling
SX50 |
2 in.
|
50 mm
|
| Solids Handling
SX50H |
3/4 in.
|
19 mm
|
| Liquids Handling |
domestic effluent and drain water
|
| Intermittent
Liquid Temp. |
up to 140°F
|
up to 60°C
|
| Windings Insulation Temp. (Class
B) |
266¾F
|
up to 60¾C
|
Motor Electrical Data
(Single phase motors are capacitor start type. Myers control panels or capacitor
kits are recommended for proper operation and warranty.) |
1/2 hp. 1750 rpm,
1 ph - capacitor start,
230 volt; 60 Hz
|
| Motor Insulation |
Class B (130¾C)
|
| Std. Third Party Approvals |
CSA, UL Class 1, Div. 1, Group D
|
| Acceptable pH Range |
6-9
|
| Specific Gravity |
.9-1.1
|
| Viscosity |
28-35 SSU
|
| Discharge, NPT SX50 |
2 in.
|
50.8 mm
|
| Discharge, NPT SX50H |
1-1/2 in.
|
38.1 mm
|
| Min. Sump Dia. Vertical |
24 in.
|
61.0 mm
|
| Min. Sump Dia. Duplex |
36 in.
|
91.4 mm
|
|
Product Performance Chart

|
|